Plant Cultivation Chamber

QQ20260713-145219.png


The core of plant culture room renovation lies in sterile sealing, constant temperature and humidity, controllable lighting, and gradient pressure difference, requiring easy-to-clean, corrosion-resistant materials and a dedicated purification air conditioning system.

Key Renovation Indicators

  • Cleanliness: Aseptic operation area should reach ISO Class 7 (10,000) to ISO Class 8 (100,000) to prevent microbial contamination.

  • Temperature & Humidity: Temperature controlled at 23-27°C (adjust per species), relative humidity at 70%-80%, requiring constant temperature and humidity air conditioning.

  • Lighting: Light intensity 1500-3000 lx, photoperiod typically 16h light/8h dark, fixtures must be recessed with heat dissipation considered.

  • Pressure Difference: Culture area maintains +10Pa positive pressure over buffer/prep rooms, with "top supply, bottom return" airflow to avoid dead zones.

Enclosure Structure & Material Requirements

  1. Flooring: Use epoxy self-leveling, anti-static PVC, or slip-resistant corrosion-resistant tiles, seamless, wear-resistant, easy to disinfect, with rounded corners to prevent dust accumulation.

  2. Walls & Ceiling: Prefer machine-made clean color steel or stainless steel panels, with sealed joints, avoid direct sunlight to prevent fading or temperature fluctuation.

  3. Doors & Windows: Install airtight automatic sliding doors or push-pull doors (reduce air disturbance), windows should be sealed or double-glazed, with ventilation windows and exhaust fans if needed.

  4. Piping: All water, electricity, and ventilation ducts must be concealed, with sealed joints to eliminate exposed dust-collecting dead zones.

Functional Zoning & System Configuration

  • Zoning Layout: Strictly separate preparation room (washing/sterilization), aseptic inoculation room (core clean area), culture room (lighting/temperature control), and acclimatization room, with buffer transitions between zones.

  • Air Conditioning & Purification: Must equip constant temperature and humidity units with HEPA filters at terminals; install UV sterilization lamps on the ceiling of the inoculation room (on when unoccupied).

  • Electrical & Lighting: Culture racks with dedicated LED grow lights (include in heat load calculation), equipped with timers for photoperiod control, circuits must be moisture and corrosion resistant.

  • Drainage & Ventilation: Floor drains must have water seals to prevent odor backflow, fresh air volume precisely calculated based on personnel and equipment heat dissipation to avoid excessive ventilation and energy waste.